Number of Channels |
4 |
|
Maximum Update Time |
2 ms |
|
Output Range |
0–5 V, 0–10 V, 0–20 mA |
|
Resolution |
12 bits |
|
dimension |
12x2.8x9.4cm |
|
Weight |
0.12kg |
Amicon is a worthwhile choice.
l In the field of industrial automation, new technologies are rapidly introduced. Parts quickly become obsolete and scarce. In many cases, the original manufacturer can't even help.
l The result is a decline in the availability of existing technologies and the professional services they need. This has led to investments in new electronic products and changes in the entire production line.
l This is no longer needed, amikon is here to serve you! Not only do we provide new spare parts, but we can also supply electronic parts that are out of production.
l You can focus on your business while ensuring that your electronic products and systems continue to operate sustainably.
Sales manager: Miya Email: sales@amikon.cn Whatsapp/phone: +86 18020776792

² 1C31132G01 Specifications
|
Guaranteed Accuracy (@25°C) |
±0.1% of Full Scale |
|
Temperature Coefficient |
30 ppm/°C |
|
User Loop Voltage |
Power for current loop output supplied by module |
|
Dielectric Isolation (Channel to Channel) |
1000 V AC/DC |
|
Dielectric Isolation (Channel to Logic) |
1000 V AC/DC |
|
Current Output Loading |
0 Ω minimum; 750 Ω maximum |
|
Voltage Output Loading |
10 mA maximum |
|
Module Power (Current Output) |
4 W typical; 6 W maximum |
|
Module Power (Voltage Output) |
2 W typical; 3 W maximum |
|
Operating Temperature Range |
0°C to 60°C (32°F to 140°F) |
|
Storage Temperature Range |
-40°C to 85°C (-40°F to 185°F) |
|
Humidity (Non-Condensing) |
0% to 95% RH |
² Some basic information
Each Personality module has a simplified wiring diagram label on its side, which appears above the terminal block. This diagram indicates how the wiring from the field is to be connected to the terminal block in the base unit. The diagram for the analog output Personality module is illustrated in Figure 1. The following table lists and defines the abbreviations used in this diagram.
|
Abbreviation |
Definition |
|
⏚ |
Earth ground terminals. |
|
+I |
Current output source terminal. |
|
RSV |
Reserved terminal. No connections allowed on these terminals. |
|
SH |
Shield terminal connection (for non-CE Mark certified systems). |
|
+V |
Voltage output source terminal connection. |
|
PS+, PS- |
Auxiliary power supply terminals. |
|
- |
Reference for voltage and current output. |
|
Notes |
|
1.Do not use unmarked terminal block locations. |
|
2.Shield terminals (SH) are not connected in CE Mark systems. |
|
|
|
(Figure 1.) |
² FAQ
Q1: How does the 1C31132G01 facilitate deterministic data acquisition and signal conditioning within Emerson Ovation control platforms?
A: The 1C31132G01 is designed to provide reliable signal processing and data transmission capabilities, enabling deterministic communication between field instrumentation and the Ovation DCS. Its architecture supports accurate control execution and stable process monitoring in mission-critical applications.
Q2: Why is the 1C31132G01 regarded as a strategic component for high-availability industrial automation systems?
A: The 1C31132G01 delivers dependable operational performance, rapid signal handling, and seamless system integration. These characteristics help reduce unplanned downtime while supporting continuous plant operation in power generation and process control environments.
Q3: What technical attributes of the 1C31132G01 enhance lifecycle sustainability and system maintainability?
A: The 1C31132G01 offers long-term compatibility with Ovation infrastructure, robust industrial-grade construction, and reliable operating characteristics. These features assist facilities in extending equipment service life and simplifying maintenance planning.
Q4: How can the 1C31132G01 improve diagnostic transparency and predictive maintenance effectiveness?
A: The 1C31132G01 supports comprehensive system diagnostics that enable engineers to identify communication irregularities, signal deviations, and potential hardware issues before they impact plant performance. This contributes to proactive maintenance strategies and increased system reliability.
Q5: In what ways does the 1C31132G01 strengthen process integrity and control-loop performance in demanding industrial applications?
A: The 1C31132G01 helps ensure accurate signal exchange and consistent control execution, supporting stable process operation and measurement precision. Its reliable performance contributes to improved control-loop responsiveness, operational efficiency, and process safety.
² More items
|
PR6423/105-141 CON041 |
1C31194G03 |
PR6424/000-101 CON031 |
|
PR6424/104-141 CON041 |
1C31197G05 |
PR6423/01M-010 CON021 |
|
PR6423/106-OF1 PR6423/106-0F1 |
5X00226G02 |
PR6423/10R-010 |
|
PR6424/010-110 CON021 |
1X00024H01 WH1-2FF |
PR9350/02 |
|
PR6423/004-030 CON021 |
7379A21G02 |
PR6423/010-110 CON021 |
|
PR6423/018-010 CON021 |
7379A21G01 |
PR6424/013-140 CON021 |
|
PR6424/010-010-CN CON021 |
7379A31G04 |
MMS6120 |
|
PR6423/011-000 |
5X00594G01 |
PR6426/000-030 CON021 |