The IM 155-6 PN ST is the PROFINET interface module at the head of a SIMATIC ET 200SP distributed I/O station. It transfers cyclic I/O, diagnostics and station status between the PROFINET controller and the installed ET 200SP modules.
01
The module supports a station with up to 32 ET 200SP I/O modules and can incorporate up to 16 ET 200AL modules. This creates a practical bridge between cabinet-mounted IP20 I/O and machine-level ET 200AL equipment.
02
Multi hot swap permits supported module groups to be exchanged while other station sections continue operating, subject to the engineered station arrangement and operating process.
03
The network connection uses a separately selected ET 200SP BusAdapter. Optional PROFINET strain relief supports orderly cable routing; the included server module 6ES7193-6PA00-0AA0 terminates the ET 200SP backplane bus.
04
PN Security Class 1 is part of this hardware generation. During replacement, verify the configured device name, IP settings, BusAdapter, server module and project support for the -6AU02 version.
Confirm the complete article number, installed system generation, field wiring, accessories, firmware and project compatibility before purchase or replacement.
SYSTEM RELATIONSHIP
Choose by architecture, not appearance
ARTICLE / FAMILY
HARDWARE ROLE
DISTINCTION
SELECTION NOTE
6ES7155-6AU02-0BN0
Multi hot swap
PN Security Class 1
Current ST generation
6ES7155-6AU01-0BN0
Single hot swap
Earlier generation
Predecessor
6ES7155-6AA02-0BN0
Multi hot swap
BusAdapter bundle
Bundle article
A correct replacement preserves the electrical interface, project support and system role. Similar housings do not guarantee interchangeable behavior.
AMIKON INDUSTRIAL SUPPLY
Reliable industrial supply
Fast, dependable delivery for current and discontinued automation parts.
QUALITY
Careful part matching, responsive support and order tracking for cross-border procurement.
Stock built around uptime
A broad international network helps shorten the route from inquiry to dispatch.
R Reliability Fast handling helps reduce avoidable downtime.
T Trust Clear communication follows each order stage.
Returns and replacement: Contact us within seven days if an issue appears after receipt. Returned goods must remain in their original condition and include a clear reason. After inspection, an eligible return or replacement will be arranged. Return shipping costs are borne by the buyer.
BUYER FAQ
Checks that protect the project
Does 6ES7155-6AU02-0BN0 include a PROFINET BusAdapter?
No. The interface module includes the server module, while the required BusAdapter is selected separately to suit the planned copper or fiber connection.
How large can a 6ES7155-6AU02-0BN0 station be?
It supports up to 32 ET 200SP I/O modules and up to 16 ET 200AL modules, subject to the complete station power and configuration limits.
Can modules be changed while 6ES7155-6AU02-0BN0 remains in service?
It supports multi hot swap. The station must be engineered for the intended exchange groups, and the process must tolerate the affected signals.
What must be checked when replacing an earlier IM with 6ES7155-6AU02-0BN0?
Check project compatibility, firmware, device name, IP settings, BusAdapter type, server module and the change from single to multi hot-swap behavior.
Why is the server module important for 6ES7155-6AU02-0BN0?
The server module closes the ET 200SP backplane bus at the end of the station. Correct placement is required for a complete station assembly.