Eight-channel voltage-input module for ET 200SP stations. It combines compact analog acquisition with module diagnostics and a 16-bit conversion format.
8 Voltage inputs
16 bit Resolution
A0/A1 BaseUnit types
Color code CC02. Confirm channel configuration, terminal assignment and input range before commissioning.
International Delivery on the Day Quick Response Support Intercontinental Cooperation Network
The AI 8xU Basic is an ET 200SP analog input module with eight voltage channels and 16-bit conversion. It fits BaseUnit types A0 and A1, uses color code CC02 and provides module diagnostics for compact multi-channel measurement.
PN
SYSTEM MATCH
TECHNICAL PROFILE
Configuration Points That Affect Fit
01
Module function
AI 8xU Basic
Eight voltage-measurement channels
02
Channel count
8 analog inputs
High channel density in one ET 200SP module
03
Signal type
Voltage input
Match each transmitter range and grounding scheme
04
Resolution
16 bit
Digital conversion across the configured range
05
BaseUnit fit
Type A0 or A1
Terminal and potential-group selection matters
06
Color code
CC02
Supports terminal assignment control
07
Diagnostics
Module diagnostics
Use station diagnostics during commissioning
08
System format
ET 200SP peripheral module
Requires a compatible ET 200SP station
MATCH THE EXACT ORDER CODE
Send clear markings and installed-system details for a focused quote.
Installation, Operation and Commissioning sequence
1
Voltage-loop design
This module is intended for voltage signals. Confirm range, common potential, sensor grounding and shield termination before connecting field wiring.
2
Channel-density benefit
Eight inputs reduce cabinet width for multi-signal applications. Higher density also makes thermal planning, cable labeling and common-potential design more important.
3
BaseUnit relationship
The card uses a AI 8xU Basic interface. Slot availability, BIOS behavior, operating system support and installed SIMATIC NET components should be checked before replacement.
4
Commissioning sequence
Check zero and span, polarity, channel mapping, open-circuit behavior, shielding, diagnostic response and scaling in the PLC program before process release.
SYSTEM RELATIONSHIP
Series Position and Selection Boundary
6ES7134-6FF00-0AA1
AI 8xU Basic; 8 channels; 16 bit
Voltage-only high-density Basic module
AI 8xI Basic variants
Current-input modules
Use for current loops rather than voltage signals
AI U/I Standard variants
Voltage and current capability by model
Broader signal flexibility with different channel density
AI RTD/TC variants
Temperature-sensor inputs
Dedicated measurement and compensation functions
Selection rule: confirm the complete order code, hardware revision, mating components, installed architecture and required behavior before shipment.
AMIKON GLOBAL AUTOMATION SUPPORT
Fast and dependable delivery We help customers obtain current and discontinued automation parts while reducing maintenance delay.
QUALITY | RELIABILITY | TRUST
Availability with accountable service Broad brand coverage, responsive coordination and transparent communication support urgent plant needs.
Customer focus Industrial automation supply Legacy-system support Order tracking Worldwide coordination
Our goal is to keep production moving through careful part matching, efficient delivery and lasting customer relationships built on quality, reliability and honest communication.
MATCH THE EXACT ORDER CODE
Send clear markings and installed-system details for a focused quote.
Contact us within 7 days after receipt if a problem appears. Keep the item in its original condition and state the specific reason. After the returned item is received and checked, an eligible return or replacement can be arranged. Return shipping remains the buyer's responsibility.
BUYER FAQ
Questions Before Ordering 6ES7134-6FF00-0AA1
Q1
Can 6ES7134-6FF00-0AA1 be used for 4 to 20 mA loops?
Do not assume direct current-loop compatibility. This model is the AI 8xU voltage-input version; select wiring and hardware that match the actual signal type.
Q2
Which BaseUnits fit 6ES7134-6FF00-0AA1?
It is specified for ET 200SP BaseUnit types A0 and A1. Confirm terminal layout and potential-group design before ordering.
Q3
What should be checked for 6ES7134-6FF00-0AA1 shield wiring?
Review sensor grounding, common potential, shield termination, cable routing and cabinet EMC practice for the complete measurement loop.
Q4
How should 6ES7134-6FF00-0AA1 channels be commissioned?
Apply known test values, confirm polarity, zero, span, scaling, channel assignment and diagnostic behavior for every used channel.
Q5
What is the main replacement risk with 6ES7134-6FF00-0AA1?
A visually similar ET 200SP analog module may use current, RTD or thermocouple inputs. Match the full order code, BaseUnit and configured signal range.