IEC 61850 ↔ ETHERNET/IP
PLX82-EIP-61850Dual Port Client Gateway
Rockwell Automation PACs can interface with IEC 61850 Intelligent Electronic Devices through a dedicated protocol gateway.
|
PROSOFT
PLX82
IEC 61850 CLIENT
|
| 24V Nominal DC supply |
2 × RJ45 10/100 Base-T ports |
20 Maximum EtherNet/IP I/O connections |
70°C Maximum operating temperature |
|
IEC 61850 CLIENT
Protocol CapabilitiesMMS — IEC 61850-8-1
BRCB — Buffered reports
URCB — Unbuffered reports
GOOSE — Normal / enhanced security
SNTP/NTP — UTC time synchronization
|
EtherNet/IP Data ArchitecturePLX82-EIP-61850 operates as an EtherNet/IP Server toward the Rockwell Automation control environment. Multiple EtherNet/IP I/O connections can provide real-time data transfer.
|
| Power 10–36 VDC input |
Temperature -25°C to 70°C operating |
Storage -40°C to 85°C |
Dimensions 11.99 × 5.1 × 10.62 cm |
|
FIELD / SUBSTATION
IEC 61850 IEDs
Relays
Power monitors Logical nodes Reports / GOOSE |
TRANSLATION CORE
PLX82-EIP-61850
IEC 61850 Client
↕
EtherNet/IP Server
|
CONTROL
Rockwell Logix
ControlLogix
CompactLogix EtherNet/IP PLC / PAC |
|
Sales Manager · Miya Zheng
Email: sales@amikon.cn Phone / WhatsApp: +86 18020776792 For a faster quotation, include Part Number, Quantity, Destination, Required Date and Machine/System. |
REQUEST QUOTATION |
| PLX82-EIP-61850 — Can the two Ethernet ports be assigned to different protocol networks? Yes. The product architecture permits IEC 61850 and EtherNet/IP to operate on separate subnets, making the gateway suitable for installations where the control and substation networks are separated. |
| PLX82-EIP-61850 — Does it support IEC 61850 reporting rather than only cyclic polling? Yes. BRCB and URCB reporting are supported in addition to MMS communication. |
| PLX82-EIP-61850 — What should be considered when estimating EtherNet/IP data size? The gateway supports up to 20 EtherNet/IP I/O connections, with maximum capacities of 10,000 bytes input and 9,920 bytes output. |
| PLX82-EIP-61850 — Can IED data be brought into a Logix project without manually rebuilding every tag? The dedicated configuration utility can generate the Add-On Instruction and transfer configured IED tag structures for use with RSLogix 5000 / Studio 5000. |
| PLX82-EIP-61850 — Does the gateway provide time synchronization? Yes. An SNTP/NTP client can periodically synchronize the gateway clock against a configured UTC time service. |
| MVME2304-0133 | RH927BN | ProSoft MVI56-MNET | F3237 | MVME2604-1151A |
| IC200CBL600C | EPRO MMS6310 | SDV541-S63/PRP | IC200CPUE05-EG | VRSF-20C-400-T3 |
| IC694CHS392A | MVME2604-1161 | 6SY7010-0AA02 | 6SY7000-0AA77 | PW481-51 |
| ProSoft MVI56-MCM | 6SY7000-0AA78 | IC693APU300 | IC693CBK001A | IS200TBAIH1CDC |
| IS200TDBTH2ABC | FBM214E | EPRO MMS6250 | 6SY7000-0AA31 | ALE111-S51 |
| FBM207 | 25A-A4P8N104 | 9375-12UNJ-3B | IC693PBM200 | MVI56E-MNETC-CC |
| EZ1080-10-00-010 | FBM247 | F7553 | EPRO MMS6220 | GHGR 31.7-3 |
| EZ1080-RM-00-010 | 6RY1801-0AA01 | S2SC70D-FA12010 | EBG VHP/2 15R | EPRO MMS6410 |
| IC693CBK001 | SS-11RS10MM-A | A5E00381705 | ProSoft MVI56E-GSC | IC200CPUE05-CF |
| ProSoft MVI69-MNET | MVI69L-MBS | ALR121-S50 | 6SL3054-0FB00-1BA0 | AN-X2-AB-DHRIO |
| PR9268/603-000 | A5E02424682-001 | PLX51-HART-4I | IC694ALG223 | IC200CPUE05 |
| IC693BEM340-DE | RLX2-IHNF-E | 8C-PAOH51 | LV-S62 | PR6423/03R-012-ZD |



Inventory Products


More than 40.000.000 products available and worldwide support