PSU
HONEYWELL / SAFETY MANAGER
FC-PSU-UNI2450U
V1.0 · Industrial Power Supply Unit
A high-capacity power supply for the Honeywell Safety Manager platform, featuring selectable DC output, high-current delivery and integrated undervoltage alarm monitoring.
|
OUTPUT
25 / 28 VDC
|
CURRENT
48 / 43 A
|
HOLD-UP
100 ms
|
PRODUCT OVERVIEW / 01
Power conversion for Safety Manager installations
FC-PSU-UNI2450U V1.0 is a Safety Manager power supply unit. It accepts AC input and provides selectable 25 VDC or 28 VDC output. Its output capacity, alarm interface and mounting requirements should be considered when planning a cabinet installation or replacement.
02 / POWER CHARACTERISTICS
Built around stable DC delivery.
|
25 VDC SETTING
48 A
Output current, −5°C to +50°C
|
28 VDC SETTING
43 A
Output current, −5°C to +50°C
|
Above 50°C, output current derating applies at 30 W/°C. The stated operating temperature range is −5°C to +70°C, subject to the specified derating conditions.
03 / ENGINEERING DATA
Technical Specifications
| Parameter |
Specification |
| AC input voltage |
110–240 VAC; operating limits 93–253 VAC |
| Input frequency |
47–63 Hz |
| No-load consumption |
13 W |
| Inrush current |
< 15 A |
| Output ripple / noise |
< 40 mVpp |
| Efficiency |
> 87% at 230 VAC |
| Storage temperature |
−25°C to +85°C |
| Operating temperature |
−5°C to +70°C, derating applies |
| Dimensions (W × H × D) |
420.5 × 140 × 90 mm |
| Weight |
5.7 kg, including cable set |
| Factory output setting |
25 VDC |
04 / CONNECTION & PROTECTION
Interfaces that matter during installation
|
AC input
IEC 60320 C20 inlet, 16 A, with retaining clip.
DC outputs
Two Phoenix PCV6-16/2-G1F-10,16 connectors with locking screws. The two output connectors are wired in parallel without a separation diode.
|
Alarm connection
Three-pole Phoenix MC 1,5/3-G-3,81 contact; 100 mA / 30 V rating.
Undervoltage response
The alarm relay de-energizes when output voltage falls below 22 VDC.
|
Dual overvoltage protection is provided. Input/output isolation is 3750 Vrms for 1 minute; input/case isolation is 2500 Vrms for 1 minute; output/case isolation is 500 VDC.
05 / INSTALLATION CONSIDERATIONS
Plan for clearance and compatibility.
|
Mounting
Vertical or horizontal mounting is supported. Vertical mounting is preferred for convection cooling.
|
Clearance
Allow 100 mm above and below for vertical mounting, or 100 mm around the unit for horizontal mounting.
|
Replacement note
V1.0 has a later V2.1 successor. Do not assume a direct form-and-fit replacement. Check the installed configuration and associated components before planning a changeover.
PRODUCT ENQUIRY
Request a quotation for FC-PSU-UNI2450U V1.0
Send the part number, quantity and destination. For replacement enquiries, please also include the current system configuration.
06 / TECHNICAL FAQ
FC-PSU-UNI2450U V1.0 — Buyer Questions
01. Can FC-PSU-UNI2450U V1.0 operate at both 25 VDC and 28 VDC?
Yes. The output selector supports 25 VDC or 28 VDC. The factory default is 25 VDC. Switch settings should only be changed when the power is off.
02. How should the output capacity of FC-PSU-UNI2450U V1.0 be assessed at higher temperatures?
The specified current is 48 A at 25 VDC or 43 A at 28 VDC from −5°C to +50°C. Above 50°C, the output must be derated at 30 W/°C.
03. What condition triggers the FC-PSU-UNI2450U V1.0 undervoltage alarm relay?
The relay de-energizes when the output voltage falls below 22 VDC. The alarm contact is rated at 100 mA / 30 V.
04. Does FC-PSU-UNI2450U V1.0 support horizontal cabinet mounting?
Yes. Both vertical and horizontal mounting are supported. Vertical mounting is preferred for convection cooling. Maintain the specified 100 mm clearance for the selected orientation.
05. Is FC-PSU-UNI2450U V1.0 a direct replacement for V2.1?
Do not assume direct form-and-fit compatibility. Associated components may also need replacement. Check the existing Safety Manager configuration before ordering or scheduling the changeover.
AMIKON SERVICE EXPERIENCE
Fast Delivery. Dependable Support.
International Delivery on the Day · Quick Response Support · Intercontinental Cooperation Network
|
Amikon Limited has been in the industry for many years and enjoys a good reputation
|
100% Brand New! Factory Sealed! Warranty: 12 months worldwide!
|
Reduce your support cost. Reply to you promptly within 24 hours We can accept T/T
|
Return & Replacement Policy
Please contact us within 7 days after receiving the item if a return or replacement is required. The product should remain in its original condition, and the reason for return must be provided. A refund or replacement will be arranged after the returned item is received and assessed. Return shipping costs are the buyer's responsibility.
PARTS CATALOGUE
Explore More Popular Models
Looking for another industrial component? Send us your required part number.
| 6ES7531-7PF00-0AB0 |
BT250 YBA250 |
ANB10D-415 |
Tecnint hte ETN 40 |
NT21-ST121-E |
| ANT502-50 |
SC310A-100-ASSY |
82408217-001 |
CVM1-CPU11-EV2 |
DCT1022 DCP100A |
| SPW482-13 |
VPS-100US |
1N/O 2N/C 774028 |
5410/EU |
430529 566-369 |
| SK250-UHF |
CM82-EZ-II-WH |
CM82-EZ-II-BK |
XFT100r2 42T90031 |
MB-FB-4R |
| V1400R16 |
NFDV561-P00 |
150-F60NBD |
SNT401-53 |
Tsr-44 |
| SPW481-53 SPW481 |
SDW-532-2SM-SC15 |
SCOPE 32XD |
FSH-Z2 |
NANO-8522E-1GZ-R13 |
| 6FS3083-3AG00 32C-TK |
D20K 508-0101-11D |
CC-12000-SENSOR-HEAD |
QLXD4-H51 |
IC200UDR010-BG |
| NDI-5503-AL |
-Myra-300-P 3P/4W |
03031-1045-0022 |
467NHP81100 |
H16x10A-R11 |
| SKDDI0764 |
DET4TCR/DET4TCR |
V5421B1058 |
YA032HR 7940021586 |
XL1000C100 |
| NFAI143-H01 |
NFBU200-S01 |
1756-IB16IF |
G4514-60610 |
SPW482-13 |
Contact for Availability
For product availability, delivery arrangements and order support, contact our sales team.