SIEMENS / SIMATIC S7-1500
6ES7513-1AL02-0AB0
CPU 1513-1 PN Central Processing Unit
Designed for demanding automation tasks within the SIMATIC S7-1500 platform, the CPU 1513-1 PN combines integrated PROFINET communication, dedicated program and data memory, and precise processing capabilities. It provides a central control solution for coordinated machine functions, process sequences and distributed automation architectures.
|
300 KB
Program Memory
|
1.5 MB
Data Memory
|
40 ns
Bit Performance
|
INDUSTRIAL CONTROL · NETWORK INTEGRATION · SYSTEM PERFORMANCE
| |
01 / PRODUCT OVERVIEW
Centralized Control for Industrial Automation
|
The Siemens 6ES7513-1AL02-0AB0 is a SIMATIC S7-1500 CPU 1513-1 PN designed to serve as the central processing unit of an automation system. It executes the user program, processes process data and coordinates communication with connected automation devices.
Its integrated PROFINET interface features a two-port switch, supporting network integration within an industrial Ethernet environment. The CPU provides 300 KB of work memory for program execution and 1.5 MB for data, with a SIMATIC Memory Card required for operation.
|
01
Program Execution
Processes control instructions and coordinates machine logic.
|
|
02
Network Communication
Connects the controller with compatible PROFINET devices.
|
| |
|
03
Data Management
Provides dedicated memory for application data and process values.
|
|
04
System Coordination
Coordinates automation tasks across the configured control architecture.
|
02 / TECHNICAL SPECIFICATIONS
Product Parameters
Key identification and engineering characteristics of the CPU 1513-1 PN.
| Parameter |
Specification |
| Manufacturer |
Siemens |
| Product Family |
SIMATIC S7-1500 |
| Product Type |
CPU 1513-1 PN |
| Order Number |
6ES7513-1AL02-0AB0 |
| Program Work Memory |
300 KB |
| Data Work Memory |
1.5 MB |
| Bit Performance |
40 ns |
| Communication Interface |
PROFINET IRT |
| Integrated Switch |
2-port switch |
| Supply Voltage |
24 V DC |
| Permissible Voltage Range |
19.2–28.8 V DC |
| Rated Current Consumption |
0.7 A |
| Maximum Current Consumption |
0.95 A |
| Backplane Bus Power Supply |
10 W |
| Backplane Bus Power Consumption |
5.5 W |
| Typical Power Loss |
5.7 W |
| Display Diagonal |
3.45 cm |
| Hardware Functional Status |
FS03 |
| Firmware Version |
V2.9 |
| Memory Card |
SIMATIC Memory Card required |
| Product Lifecycle |
Cancelled / Spare Part |
03 / ENGINEERING & APPLICATION
How the CPU Fits into an Automation System
The CPU 1513-1 PN operates as the central processing component of an S7-1500 automation station. It executes the configured control program, handles internal data processing and exchanges information with connected devices through its integrated PROFINET interface.
|
INPUT / OUTPUT
Signal acquisition and field control
|
→ |
CPU 1513-1 PN
Program execution and data processing
|
→ |
OUTPUT
Machine and process response
|
Typical Application Areas
• Automated production equipment and assembly lines
• Industrial machinery and coordinated motion-related control architectures
• Process monitoring and equipment control
• Distributed I/O and PROFINET-connected automation systems
• Machine communication and centralized logic processing
04 / INSTALLATION & CONFIGURATION
Important Integration Considerations
|
01
|
Verify the Mounting Position
Install the CPU in the appropriate S7-1500 rack configuration and verify compatibility with the selected mounting rail and adjacent modules.
|
|
02
|
Check the 24 V DC Supply
Confirm the supply voltage remains within the specified 19.2–28.8 V DC range and that the power supply can support the required load.
|
|
03
|
Prepare the SIMATIC Memory Card
A SIMATIC Memory Card is required. Confirm the card is suitable for the controller and contains the intended application configuration.
|
|
04
|
Configure the PROFINET Network
Assign appropriate network parameters, device names and communication settings. Check the connected device topology before commissioning.
|
|
05
|
Verify the Engineering Environment
For firmware V2.9, STEP 7 TIA Portal V17 or later is indicated for configuration. Check the actual firmware and project compatibility before downloading the program.
|
05 / COMMUNICATION & PERFORMANCE
PROFINET IRT Integration
The integrated PROFINET interface provides two switched ports, allowing compatible network devices to be connected within an industrial Ethernet topology. PROFINET IRT supports applications requiring synchronized communication and predictable data exchange.
Key Communication Characteristics
| Interface technology |
PROFINET IRT |
| Integrated ports |
2-port switch |
| Bit processing performance |
40 ns |
| Isochronous mode |
Supported |
Engineering Note
For distributed isochronous operation, the specified minimum OB 6x cycle is 500 μs; for central isochronous operation, it is 1 ms. Actual project configuration must be checked against the connected hardware and application requirements.
06 / PRODUCT EVOLUTION
CPU 1513-1 PN and Its Successor
For replacement planning, compare the original CPU with its designated successor at the hardware, memory and engineering levels.
| Feature |
6ES7513-1AL02-0AB0 |
6ES7513-1AM03-0AB0 |
| CPU Type |
CPU 1513-1 PN |
CPU 1513-1 PN |
| Program Memory |
300 KB |
600 KB |
| Data Memory |
1.5 MB |
2.5 MB |
| Bit Performance |
40 ns |
6 ns |
| PROFINET |
IRT, 2-port switch |
IRT, 2-port switch |
Replacement Compatibility Matters
A successor designation does not automatically guarantee direct interchangeability. Review the hardware configuration, firmware, project version, memory requirements, communication settings and system dependencies before replacement.
AMIKON LIMITED / ESTABLISHED 2005
20 Years of Excellence.
One Global Automation Network.
Founded in Hong Kong in 2005, Amikon is a global supplier of industrial automation parts and control system components. Two decades of development reflect the dedication, experience and commitment of its team.
Since 2005, Amikon has continuously expanded its product range and customer network. Its portfolio covers PLCs, HMIs, DCS components, panel controllers, industrial PCs and variable frequency drives.
Working with manufacturers and system integrators around the world, Amikon supports the maintenance and extended service life of existing industrial automation systems through a broad selection of components from leading OEMs.
GLOBAL TEAM
|
QUALITY CHECK
|
INTERNATIONAL INVENTORY NETWORK
Supporting industrial automation requirements worldwide
|
|
20+
Years of Experience
|
Global
Customer Network
|
Multi-OEM
Automation Portfolio
|
|
✉
|
Contact Our Sales Team
Sales Manager: Miya Zheng
|
07 / PURCHASING & REPLACEMENT
What to Confirm Before Ordering
| Exact Order Number |
Confirm 6ES7513-1AL02-0AB0, including every character and suffix. |
| |
| Hardware Status |
Check the hardware functional status and the installed firmware version. |
| |
| Memory Card |
Confirm whether a suitable SIMATIC Memory Card is available for commissioning. |
| |
| Application Compatibility |
Review TIA Portal version, program requirements and connected hardware. |
| |
| Product Condition |
Confirm the actual condition, packaging, availability and warranty terms before purchase. |
Lifecycle Consideration
Siemens identifies this order number as a cancelled product and spare part. The cancellation effective date is April 1, 2025. For an existing installation, verify the exact hardware revision and replacement requirements before selecting a substitute.
08 / AFTER-SALES SUPPORT
Return & Replacement Arrangements
|
01
|
Seven-Day Notification Period
Contact our team within 7 days of receiving the item if any issue or concern arises.
|
|
02
|
Return Condition
Returned products must remain in their original condition. Please provide the specific reason for the return.
|
|
03
|
Return or Replacement Processing
After the returned item has been received and assessed, an appropriate return or replacement arrangement will be processed. The buyer is responsible for the shipping costs incurred.
|
NEED A SPECIFIC AUTOMATION COMPONENT?
Let's Discuss Your Requirements.
Contact Miya Zheng for model confirmation, availability enquiries and order coordination.
|
Sales Manager
Miya Zheng
|
WhatsApp
86-18020776792
|
09 / TECHNICAL FAQ
Frequently Asked Questions
Practical considerations for engineering teams, maintenance personnel and purchasing departments.
Q1. Can the Siemens 6ES7513-1AL02-0AB0 operate without a SIMATIC Memory Card?
No. A SIMATIC Memory Card is required for this CPU. Before commissioning or replacing an existing unit, check that a suitable card is available and that the required application data and configuration are prepared for the intended controller.
Q2. Which STEP 7 TIA Portal version is appropriate for the 6ES7513-1AL02-0AB0?
For firmware V2.9, STEP 7 TIA Portal V17 or later is specified for configuration and integration. The actual installed firmware must be checked before project migration or download. Earlier engineering environments may require a different device configuration, so project compatibility should be verified rather than assumed.
Q3. What should be checked when replacing a 6ES7513-1AL02-0AB0 with its successor 6ES7513-1AM03-0AB0?
Although both belong to the CPU 1513-1 PN family, the successor has different memory capacities and processing performance. Check the hardware configuration, firmware compatibility, TIA Portal project, memory card, communication setup and any application-specific dependencies. A successor model should not be treated as a plug-and-play replacement without engineering verification.
Q4. How should the PROFINET IRT ports on the 6ES7513-1AL02-0AB0 be used in an existing network?
The integrated two-port switch allows compatible PROFINET devices to be connected within the network topology. When using IRT, verify the topology, synchronization requirements, device capabilities and engineering configuration. Network design and timing settings must match the actual automation application.
Q5. What should maintenance teams verify before installing a replacement 6ES7513-1AL02-0AB0?
Check the complete order number, hardware functional status, firmware version, supply voltage, SIMATIC Memory Card and the existing project configuration. Also record the PROFINET device names, network parameters and connected modules before removing the original controller. This helps reduce commissioning errors and unexpected communication interruptions.
AMIKON LIMITED
Your Automation Parts Partner
For enquiries about Siemens 6ES7513-1AL02-0AB0 and other industrial automation components, contact our sales team.
10 / MORE AUTOMATION COMPONENTS
More Popular Models
Explore additional industrial automation components from various manufacturers.
| 6SE7037-0EJ84-1JC2 |
MOD600ADOM4R |
| 6ES7041-8EK85-1HA0 |
KJ4110X1-BC1 |
| HP400ULM |
SAI533-H33/PRP |
| 6SL3200-0SP01-0AA0 |
1756-CN2R/B |
| GI357.Z74 |
VPORT451-T |
| 6SE7041-8HK85-1HA0 |
Adam-5050 |
| 914-1061-000 |
6SE7036-1EE85-1HA0 |
| BS-00-1324 |
ECN-S2 |
| C98043-A1682-L1 |
KJ3243X1-BK1 |
| WVR7120 |
1250-0.1FN |
| 6SE7041-8EK85-0HA0 |
NFDV561-P00 |
| M550S M550S-UHF |
IME539-1ERS |
| 6SE7041-8EK85-1HA0 |
Y8001-5343 |
| RD4000T3 |
CLSE3L230 |
| KJ2006X1-BK1 |
SS-350H |
| VS2EXR-24 |
ECN-S2 |
| ABB 411102-DA |
SAI533-H33/PRP |
| 6SL3350-6TK00-0EA0 |
MY8-AE96S |
| EN0027-00 |
QG2VP02NDM |
| MOD600ADOM4R |
6SE7037-0EJ84-1JC2 |
| PE1938/02 |
LRF3-SSM-WH |
| GEO20A1R03A01 |
6SE7041-8HK85-1HA0 |
| 914-1061-000 |
US-24-500W |
| KJ4110X1-BB1 |
DJ-A96 |
| NFDV561-P00 |
AKB336-M025 |
Explore More Automation Products
Contact our team for additional model enquiries and product availability.
AMIKON LIMITED
Industrial Automation Parts & Control System Components
Established in Hong Kong · 2005