GE PAC8000 / ANALOG OUTPUT
8102-HO-IPEight-Channel 4-20 mA Output with HARTA PAC8000 process I/O module with eight single-ended current outputs, HART pass-through, variable and status reporting, and per-channel open-circuit detection. |
![]() |
| 8 CHANNELS | 4-20 mA | HART |
| Sales manager Miya zheng |
Email sales@amikon.cn | WhatsApp 86-18020776792 |
| Channels | 8 single-ended | Nominal output | 4 to 20 mA |
| Full range | 1 to 23 mA | Compliance | 20 mA into 700 ohms at 21.6 V DC |
| Accuracy | +/-0.25% of span | Resolution | 12 bits |
| Open-loop threshold | 0.7 +/-0.25 mA | Ripple | Less than 0.02% of span |
| Response | 25 ms current mode; 0.75 s per HART channel | Isolation | 100 V AC, channel to Railbus |
| Field power | 24 V DC +/-10%, 300 mA maximum | Railbus current | 100 mA typical; 150 mA maximum |
| Module key | A4 | Width / weight | 42 mm / 200 g |
| 1. LOOP DATA
Record load resistance, cable length, field device and current demand for all eight channels. |
2. HART DUTY
Confirm pass-through, variable reporting, status reporting and handheld access. |
3. HARDWARE FIT
Match A4 keying, field terminal, Railbus position and bussed field power. |
| Quote package: full module label, revision, carrier position, terminal code, configuration scope and quantity. |
| Model | Core role | When to use |
|---|---|---|
| 8102-HO-IP FEATURED MODEL |
8-channel HART analog output | Use for 4-20 mA output loops requiring HART access. |
| 8104-AO-IP | 8-channel analog output | Use where HART service is not required. |
| 8101-HI-TX | HART analog input | Use for receiving transmitter current and HART variables. |
| 8103-AI-TX | Standard analog input | Use for non-HART 4-20 mA input signals. |
![]() ![]() ![]() |
AMIKON LIMITEDProfessional service. More expertise and more choices. Faster global response. |
| Sales manager Miya zheng |
Email sales@amikon.cn | WhatsApp 86-18020776792 |
| Q1 | Does GE 8102-HO-IP operate without field power?
No. It requires 24 V DC bussed field power within the specified tolerance.
|
| Q2 | Can 8102-HO-IP replace 8104-AO-IP directly?
Confirm HART scope, configuration, carrier, terminal type and project setup first.
|
| Q3 | What loop load must be checked?
At 21.6 V DC supply, compliance is 20 mA into 700 ohms including field wiring.
|
| Q4 | How should a used 8102-HO-IP be tested?
Test all eight outputs, open-loop detection, HART access, status reporting and isolation.
|
| Q5 | Which field terminal should be ordered?
Choose standard, fused, non-incendive or non-incendive fused hardware for the installation.
|
| 38500148-300 | 7402-040-01 | 6ES5482-4UA20 | C7076A1015 | 1C31203G01 |
| 6ES5430-4UA12 | 2097-V34PR5-LM | LV429386 | SDCS-DSL-4 | 1783-US08T |
| IC630CHS308 | C100/0200/STD | MPL-B230P-EJ44AA | IC630CCM300 | SDCS-POW-1 |
| A3C40173228 | GHQ6310062R0111 | 07KT92 GJR5250500R0262 | 1785-BCM/C | DDNP1501 |
| SD833 3BSC610066R1 | 80026-044-06 | TSXPSY2600 | 136188-02 | 80190-100-01-R |
| H3DE-S1 | 146031-01 | ADV551-P50 S2 | SR2E201BD | 172103-01 |
| ATA4D-00 S2 | 3RP2525-1BW30 | 3500/25 149369-01 | EB501-50 S2 | L5504AMP |
| 3500/33 149986-01 | AAI143-H53 S1 | 6ES7195-7KF00-0XA0 | 3500/20 125744-02 | SDV144-S63 S4 |
| 6DD1607-0EA1 | 51403776-100 | AAI543-H03 S1 | 6DD1683-0BC0 | 51402497-200 |
| T7412B1008 | 6SE3122-4DG40 | TK-HAO081 | LG-003842 | 6ES5304-3UB11 |
After-delivery support01 Contact within 7 days with order details and photographs.
02 Retain the item, packing and accessories in original condition. 03 Approved return or replacement follows inspection; return freight is paid by the buyer. |
|



Inventory Products


More than 40.000.000 products available and worldwide support