1771-OZL0-24V Relay Contact Output Module
An eight-point normally-open relay contact module for low-power resistive AC or DC switching in a 1771 I/O chassis. |
![]() |
| 8 Form A contacts | 4 groups of 2 | 0-24V AC/DC |
| Sales manager: Miya zheng | Email: sales@amikon.cn | WhatsApp: 86-18020776792 |
| Outputs per module | 8, arranged as 4 groups of 2 |
| Contact configuration | 8 Form A, normally open |
| Voltage rating | 0-24V AC rms or 0-24V DC |
| Current rating | 100mA maximum per output |
| Power rating | 2.4W per output, resistive load |
| Minimum contact load | 1mA at 0-24V AC or DC |
| Operate / release time | 1ms maximum |
| Switching frequency | 10Hz maximum |
| Backplane current | 420mA maximum |
| Isolation | 1000V open contacts; 1500V coil to contact |
| Field wiring arm | 1771-WD |
| Environment | 0 to 60 deg C; 5% to 95% RH, noncondensing |
| STEP 01 | Confirm contact duty Keep each resistive load within 100mA and 2.4W while accounting for every transient. |
|
| Map the four commons Record all four two-channel groups and their common conductors before rewiring. |
STEP 02 | |
| STEP 03 | Plan surge suppression The module provides no surge limiting; add suitable suppression wherever the connected circuit requires it. |
|
| Model | Main difference | When to use |
| 1771-OZL | Relay contact; 0-24V AC/DC; 100mA | Choose for low-level isolated contact switching. |
| 1771-OB | Solid-state DC; 10-27V; 1.5A per point | Choose for higher-current DC solenoids, indicators or starters. |
| 1771-OA | AC output module | Choose when the installed load and wiring require a dedicated AC output stage. |

Automation components for PLC, DCS, robot, turbine-control and condition-monitoring systems. Our team coordinates exact catalog matching and practical order support for active and legacy installations.
[01] Broad product coverage helps buyers consolidate difficult automation requirements while maintaining exact model and revision control.
[02] Experienced matching focuses on electrical duty, installed hardware and connection compatibility.
[03] Responsive coordination supports international orders and time-sensitive maintenance needs.
Email Miya zheng WhatsApp|
Q1 / ALLEN-BRADLEY 1771-OZL LOADS
Which loads are appropriate for Allen-Bradley 1771-OZL?
Use low-power resistive AC or DC circuits within 24V, 100mA and 2.4W per output. |
Q2 / ALLEN-BRADLEY 1771-OZL SOLENOIDS
Can Allen-Bradley 1771-OZL drive a solenoid directly?
Only when steady current, inrush and suppression remain within every contact limit. |
|
Q3 / ALLEN-BRADLEY 1771-OZL MINIMUM LOAD
Why does the Allen-Bradley 1771-OZL minimum load matter?
Very small loads can be unreliable on relay contacts; confirm at least 1mA at the selected voltage. |
Q4 / ALLEN-BRADLEY 1771-OZL SUBSTITUTION
Can Allen-Bradley 1771-OZL replace 1771-OB?
No direct substitution should be assumed because switching technology, ratings, wiring arm and commons differ. |
|
Q5 / ALLEN-BRADLEY 1771-OZL STARTUP
What should be tested before Allen-Bradley 1771-OZL enters production?
Check every group common, contact operation, suppression, field voltage, load current and commanded safe state. |
|
| A6740-12-N | CP451-10 | 6ES5304-3UB11 | IS210HSLAH1A | A2SAT105-S000 |
| 330103-00-08-05-02-00 | 330901-05-65-05-11-05 | A6822 | UT55A-001-11-00 | 21000-28-10-00-098-04-02 |
| 8750-CA-NS | IS220AEPBH1BAA | IS220PSCAH1B | 330180-X0-05 | 7400150-270 |
| 3500/65 | DS822.OD110 | 1771-ASB/E | IQS900 | SC4A-S-PR-NN-002-05-T1 |
| CP471-00 | SOIA-01 | PR6424/00A-110 | 160765-10 | ADV569-P00 |
| 6DP1641-8AA | PR6424/006-030 | EC402-51 | 330101-00-63-10-02-00 | 6ES5756-0AA11 |
| A3120/022-000 | FU20-05-T1-NPT | 330106-05-30-15-02-CN | IS220PCLAH1A | KL4104X1-BA1 |
| CP471-01 | 330130-030-01-CN | 7400166-380 | AAI143-S00 | 330180-51-00 |
| IMASI13 | 7400195-210 | 145988-02 | 204-450-000-002 | WDP5-118.051-00 |
| FLXA21-D-P | KL2101X1-BB1 | SAI143-S63 | 6AU1425-2AD00-0AA0 | AIP830-101 |
| AFTER-DELIVERY SUPPORT | ||
| 01 / CONTACT Contact us within 7 days with order details, photographs and a clear description. |
02 / CONDITION Retain original condition, packaging and all supplied accessories. |
03 / RESOLUTION Resolution follows receipt and inspection; return shipping remains the buyer's responsibility. |
| Sales manager: Miya zheng | sales@amikon.cn | WhatsApp: 86-18020776792 |



Inventory Products


More than 40.000.000 products available and worldwide support